Evaporative Cooling Pad Saturation Effectiveness & Water Loss Calculator

Direct evaporative cooling utilizes the adiabatic heat exchange between dry ambient air and recirculated water trickling through corrugated cellulose or fiberglass media pads.

Hot dry ambient air temperature entering the cooling pad face.

Ambient wet-bulb thermodynamic limit for direct evaporative cooling.

Manufacturer media saturation efficiency (typically 75-85% for 100mm pads, 85-92% for 150mm pads).

Supply fan volumetric airflow rate through the pad media.

Calculated Result
24.4 °C

Leaving Dry-Bulb Temp

Temperature Drop (ΔT)

13.6 °C

Sensible Cooling Duty

22.4 kW

Water Evaporation Rate

32.91 L/h

Saturation Efficiency

85%

Calculation Breakdown

  1. Wet-Bulb Depression & Temperature DropWet-Bulb Depression = (38 - 22) = 16.0 °C; ΔT = 0.85 · 16.0 = 13.6 °C
  2. Leaving Supply Air Dry-Bulb TemperatureT_db,out = 38 - 13.6 = 24.4 °C
  3. Sensible Capacity & Water Evaporation RateCooling Duty = 22.4 kW; Make-up Water Consumption = 32.91 L/h

Evaporative Cooling Thermal Response

Interactive visualization based on your current inputs

Value
0.09.5192938Ambient Tdb (°C)Wet Bulb Twb (°C)Supply T (°C)Cooling (kW)ParameterValue

What Is the Evaporative Cooling Pad Saturation Effectiveness & Water Loss Calculator?

Direct evaporative cooling utilizes the adiabatic heat exchange between dry ambient air and recirculated water trickling through corrugated cellulose or fiberglass media pads.

Water absorbs sensible latent heat from passing airflow, evaporating and humidifying the stream while lowering air dry-bulb temperature toward the entering wet-bulb temperature.

This calculator predicts the discharged air dry-bulb temperature, sensible cooling tonnage, and required water make-up supply rate based on pad saturation effectiveness.

How Does the Evaporative Cooling Pad Saturation Effectiveness & Water Loss Calculator Work?

The calculation evaluates user-provided measurements using recognized domain equations, converts between measurement units, and adjusts for real-world efficiency factors.

Evaporative Cooling Pad Saturation Effectiveness & Water Loss Calculator Formula & Variables

The core mathematical equation utilized by this calculator is expressed as:

T_{leaving} = T_{db} - \eta_{sat} \left(T_{db} - T_{wb}\right), \quad \dot{m}_{water} = \frac{Q_{sensible}}{h_{fg}} \times 3600

Adiabatic saturation effectiveness relationship and latent heat mass conservation across wet media.

How to Use the Evaporative Cooling Pad Saturation Effectiveness & Water Loss Calculator

  1. Enter your primary measurements in the input fields above.
  2. Select your preferred units (e.g. metric or imperial) if applicable.
  3. Review or adjust operational assumptions such as field efficiency.
  4. Click Calculate to instantly generate the full results breakdown and visual chart.
  5. Use the Reset button at any time to clear the form and test a new scenario.

Step-by-Step Example Calculation

Dry Summer Greenhouse (38°C Dry-Bulb, 22°C Wet-Bulb, 85% Pad)

Input Values:

enteringAirDryBulbC:38.0
enteringAirWetBulbC:22.0
padSaturationEfficiencyPercent:85
airVolumetricFlowRateM3h:5000
Worked Steps: Cools air by 13.6°C down to 24.4°C, providing 22.8 kW sensible cooling while evaporating 33.5 liters/hour of water.

Understanding Your Result

Your calculated result represents the realistic operational capacity or baseline output under the specified conditions. Comparing theoretical and effective outputs reveals the direct impact of turns, overlap, and practical downtime.

Factors That Affect the Result

Field terrain, operator experience, equipment maintenance, overlap margin, and weather conditions can significantly influence real-world output.

When Should You Use This Calculator?

Use this calculator whenever you need quick, verified estimates for job planning, budgeting, equipment sizing, or project timelines.

Assumptions & Limitations

  • Leaving Air Temperature: T_leaving = T_db - (η_sat / 100) · (T_db - T_wb).
  • Sensible Temperature Drop: ΔT = T_db - T_leaving.
  • Sensible Cooling Capacity: Q_sensible = ρ_air · c_p · V · ΔT / 3600 (kW).
  • Water Evaporation Consumption: m_water ≈ Q_sensible / h_fg · 3600 (kg/h or L/h, with h_fg ≈ 2450 kJ/kg).