Skip to main content

HVAC Sensible & Latent Cooling Load Supply Airflow Calculator

Conditioning an indoor space requires supplying air at a sufficiently cold temperature and low moisture content to absorb occupants, equipment, and solar heat gains.

Room sensible heat gain (conduction, solar, lights, computers, occupant sensible heat).

Room latent heat gain (occupant perspiration, kitchen steam, infiltration vapor).

Thermostat setpoint dry-bulb temperature (typically 22 - 25°C).

Air delivery temperature leaving AHU supply diffuser (typically 12 - 14°C).

Calculated Result
6,784 m³/h

Required Airflow

Volumetric Flow in CFM

3,993 CFM

Mass Flow Rate

2.261 kg/s

Sensible Heat Ratio (SHR)

0.83

Supply Air ΔT

11.0 °C

Calculation Breakdown

  1. Space Temperature DifferentialΔT = T_room - T_supply = 24 - 13 = 11.0 °C
  2. Required Mass Flow Ratem_dot = Q_s / (c_p · ΔT) = 25 kW / (1.005 · 11.0) = 2.261 kg/s
  3. Volumetric Airflow DemandAirflow = 6,784 m³/h (3,993 CFM) with SHR = 0.83

HVAC Airflow & Cooling Metrics

Interactive visualization based on your current inputs

Value
0.09.9203040Sensible Load (kW)Latent Load (kW)CFM / 100Mass Flow (kg/s)ParameterValue

What Is the HVAC Sensible & Latent Cooling Load Supply Airflow Calculator?

Conditioning an indoor space requires supplying air at a sufficiently cold temperature and low moisture content to absorb occupants, equipment, and solar heat gains.

Supply airflow rate is sized primarily by the sensible heat equation to offset room dry-bulb temperature gains, while the coil apparatus dew point handles latent condensation loads.

This calculator computes dry air mass flow in kg/s, volumetric airflow in both m³/h and CFM, and Sensible Heat Ratio (SHR) to size central AHUs and VAV air handlers.

How Does the HVAC Sensible & Latent Cooling Load Supply Airflow Calculator Work?

The calculation evaluates user-provided measurements using recognized domain equations, converts between measurement units, and adjusts for real-world efficiency factors.

HVAC Sensible & Latent Cooling Load Supply Airflow Calculator Formula & Variables

The core mathematical equation utilized by this calculator is expressed as:

\dot{m} = \frac{Q_s}{c_p (T_{room} - T_{supply})}, \quad V = \frac{\dot{m}}{\rho_{air}}, \quad SHR = \frac{Q_s}{Q_s + Q_l}

First law steady sensible enthalpy balance governing forced convection air conditioning systems.

How to Use the HVAC Sensible & Latent Cooling Load Supply Airflow Calculator

  1. Enter your primary measurements in the input fields above.
  2. Select your preferred units (e.g. metric or imperial) if applicable.
  3. Review or adjust operational assumptions such as field efficiency.
  4. Click Calculate to instantly generate the full results breakdown and visual chart.
  5. Use the Reset button at any time to clear the form and test a new scenario.

Step-by-Step Example Calculation

Commercial Office Suite (25 kW Sensible, 5 kW Latent, 11°C ΔT)

Input Values:

roomSensibleHeatLoadKW:25.0
roomLatentHeatLoadKW:5.0
roomDesignDryBulbC:24.0
supplyAirDryBulbC:13.0
Worked Steps: Requires 2.26 kg/s (6748 m³/h or 3971 CFM) supply air at SHR = 0.833.

Understanding Your Result

Your calculated result represents the realistic operational capacity or baseline output under the specified conditions. Comparing theoretical and effective outputs reveals the direct impact of turns, overlap, and practical downtime.

Factors That Affect the Result

Field terrain, operator experience, equipment maintenance, overlap margin, and weather conditions can significantly influence real-world output.

When Should You Use This Calculator?

Use this calculator whenever you need quick, verified estimates for job planning, budgeting, equipment sizing, or project timelines.

Assumptions & Limitations

  • Sensible Heat Balance: Q_s = m_dot · c_p · (T_room - T_supply).
  • Air specific heat c_p ≈ 1.006 kJ/(kg·K); standard air density ρ ≈ 1.204 kg/m³.
  • Required Air Mass Flow: m_dot = Q_s / [1.006 · (T_room - T_supply)] in kg/s.
  • Volumetric Flow Rate: V = (m_dot / ρ) · 3600 in m³/h (1 m³/h ≈ 0.5886 CFM).
  • Sensible Heat Ratio: SHR = Q_s / (Q_s + Q_l).

Frequently Asked Questions

Calculation Accuracy & Reference Note

This calculator implements verified, deterministic mathematical equations based on published standards. Results should be treated as professional engineering estimates; always verify critical operations with local equipment manuals and site inspections.

Explore more tools and calculators in Education Calculators