Three-Phase Transformer kVA & FLA Sizing Calculator

Commercial electrical services frequently step down 480V three-phase delta down to 208Y/120V wye for building distribution.

Standard 3-phase ratings: 15, 30, 45, 75, 112.5, 150, 225, 300, 500 kVA.

High-voltage supply side (e.g. 480V).

Low-voltage distribution side (e.g. 208V).

Calculated Result
208.2 Amps FLA

Secondary Full-Load Current

Primary Full-Load Current

90.2 Amps FLA

Secondary OCPD Breaker

270 A

Primary OCPD Breaker

115 A

Three-Phase kVA Rating

75 kVA

Calculation Breakdown

  1. Secondary Full-Load Current (FLA)I_sec = (75 kVA × 1,000) ÷ (√3 × 208 V) = 208.2 Amps
  2. Primary Full-Load Current (FLA)I_pri = (75 kVA × 1,000) ÷ (√3 × 480 V) = 90.2 Amps
  3. Overcurrent Protection Sizing (NEC 450.3)Secondary main protection sized for 270A (125% FLA rule)

Secondary Full-Load Amps (FLA) at 208V Across Transformer Sizes

Interactive visualization based on your current inputs

Calculated Value
0.010420831241630 kVA45 kVA75 kVA112.5 kVA150 kVA

What Is the Three-Phase Transformer kVA & FLA Sizing Calculator?

A three-phase transformer uses electromagnetic induction to step voltage levels up or down between three-phase electrical circuits while preserving power frequency.

How Does the Three-Phase Transformer kVA & FLA Sizing Calculator Work?

Solves secondary Full-Load Amps: I = (kVA × 1,000) ÷ (1.732 × V_secondary).

Solves primary Full-Load Amps: I = (kVA × 1,000) ÷ (1.732 × V_primary).

Rounds up overcurrent protection device (OCPD) ratings using the 125% rule specified in NEC Table 450.3(B).

Three-Phase Transformer kVA & FLA Sizing Calculator Formula & Variables

The core mathematical equation utilized by this calculator is expressed as:

FLA = (kVA × 1,000) ÷ (√3 × V_LL)

Standard three-phase apparent power formula where current is inversely proportional to square root of 3 (1.732) times line-to-line voltage.

How to Use the Three-Phase Transformer kVA & FLA Sizing Calculator

  1. Select transformer kVA rating.
  2. Enter primary and secondary line-to-line voltage.
  3. Read full-load amps and recommended breaker ratings for both sides.

Step-by-Step Example Calculation

75 kVA 480V Primary to 208V Secondary Transformer

Input Values:

kvaRating:75
primaryVoltageV:480
secondaryVoltageV:208

Understanding Your Result

Provides primary and secondary FLA for sizing feed conductors, lugs, and main disconnect breakers.

Factors That Affect the Result

  • Inrush current (typically 8x to 12x FLA during initial coil magnetization).

When Should You Use This Calculator?

  • Commercial electrical build-outs, manufacturing plant feeder design, and utility service entrance planning.

Assumptions & Limitations

  • Three-phase balanced load operation.

Frequently Asked Questions

Calculation Accuracy & Reference Note

National Electrical Code (NEC 450.3 / NFPA 70) compliant calculation.