Centrifugal Pump Affinity Laws Calculator (Flow, Head, Power)

The centrifugal pump affinity laws mathematically describe how flow rate, head, and shaft power vary as impeller rotational speed or diameter changes.

Baseline operational pump rotational speed in RPM.

Adjusted pump speed (e.g., 1440 RPM represents an 80% speed modulation via VFD).

Volumetric discharge flow rate at baseline speed in m³/h (or GPM).

Baseline developed pump head pressure in meters (or feet).

Baseline electric motor brake horsepower or shaft power in kW.

Baseline impeller outer diameter in mm (default 250 mm).

Trimmed impeller diameter (keep equal to D₁ if speed modulation only).

Calculated Result
7.68 kW

New Shaft Power (Cube Law)

New Flow Rate (Q₂)

80 m³/h (80% of baseline)

New Head Pressure (H₂)

28.8 m (64.0% of baseline)

New Shaft Power (P₂)

7.68 kW (51.2% of baseline)

VFD Power Savings

7.32 kW (48.8% reduction)

Speed Adjustment Ratio (N₂ / N₁)

0.8x

Calculation Breakdown

  1. 1. Speed Scaling RatioSpeed Ratio = 1440 RPM / 1800 RPM = 0.8
  2. 2. Affinity Laws ApplicationFlow Q₂ = Q₁ · (0.8) = 80 m³/h; Head H₂ = H₁ · (0.8)² = 28.8 m; Power P₂ = P₁ · (0.8)³ = 7.68 kW
  3. 3. Energy Efficiency Impact (Cube Law)A 20% speed reduction reduces brake power from 15 kW to 7.68 kW, saving 7.32 kW.

Pump Power vs Speed Ratio (% Baseline)

Interactive visualization based on your current inputs

Power (%)
0.025507510060% Speed70% Speed80% Speed90% Speed100% SpeedSpeed Ratio (% N₁)Power (% P₁)

What Is the Centrifugal Pump Affinity Laws Calculator (Flow, Head, Power)?

The pump affinity laws are hydraulic similitude relationships predicting performance changes in rotodynamic pumps subjected to speed or impeller geometry adjustments.

How Does the Centrifugal Pump Affinity Laws Calculator (Flow, Head, Power) Work?

Rooted in Euler’s turbomachinery equations, fluid velocity scales linearly with tip speed, static pressure with dynamic head (v²), and energy transfer with rate of momentum change.

Centrifugal Pump Affinity Laws Calculator (Flow, Head, Power) Formula & Variables

The core mathematical equation utilized by this calculator is expressed as:

\frac{Q_2}{Q_1} = \frac{N_2}{N_1}, \quad \frac{H_2}{H_1} = \left(\frac{N_2}{N_1}\right)^2, \quad \frac{P_2}{P_1} = \left(\frac{N_2}{N_1}\right)^3

Flow scales linearly with speed ratio. Pressure head scales quadratically with speed ratio. Shaft power scales with the cube of speed ratio.

How to Use the Centrifugal Pump Affinity Laws Calculator (Flow, Head, Power)

  1. Enter baseline pump speed, flow, head, and shaft power.
  2. Specify target operating speed or trimmed diameter.

Step-by-Step Example Calculation

20% Speed Reduction on 15 kW Pump (1800 to 1440 RPM)

Input Values:

initialSpeedRpm:1800
targetSpeedRpm:1440
initialFlowM3H:100
initialHeadMeters:45
initialPowerKw:15
initialDiameterMm:250
targetDiameterMm:250
Worked Steps: Dropping speed to 80% reduces flow to 80 m³/h, head to 28.8 m, and slashes power consumption from 15 kW down to 7.68 kW (48.8% energy savings!).

Understanding Your Result

Target Flow (Q₂): New volumetric discharge capacity.

Target Head (H₂): New pressure head delivered across pump suction and discharge.

Target Power (P₂): New brake shaft kilowatt requirement.

Power Savings: Realized kilowatt reduction and percentage energy conserved.

Factors That Affect the Result

  • Speed adjustment ratio has cubic impact on electricity demand.

When Should You Use This Calculator?

  • HVAC hydronic chilled water systems, municipal wastewater lift stations, industrial process cooling, and energy audit retrofits.

Assumptions & Limitations

  • Assumes constant hydraulic efficiency and negligible static lift (friction-dominated piping circuits).

Frequently Asked Questions

Calculation Accuracy & Reference Note

Standard Hydraulic Institute (HI) centrifugal pump affinity relationships.