Per-Unit System Impedance Base Conversion Calculator

The per-unit system normalizes electrical quantities against reference base values, eliminating ideal transformer turns ratios in multi-voltage power grids.

Nameplate per-unit impedance.

Equipment rated line-to-line voltage.

Equipment rated 3-phase apparent power.

System bus reference voltage base.

Common system-wide study power base (often 100 MVA).

Calculated Result
0.3200 p.u.

New Per-Unit Impedance

Physical Impedance (Ohms)

0.609 Ω

Original Base Impedance

7.62 Ω

New Base Impedance

1.90 Ω

Calculation Breakdown

  1. Original Base Impedance (Z_base,old)(kV_old)^2 / MVA_old = (13.8)^2 / 25 = 7.618 Ω
  2. Actual Physical Impedance (Z_ohms)Z_pu,old * Z_base,old = 0.08 * 7.618 = 0.609 Ω
  3. New Base Impedance (Z_base,new)(kV_new)^2 / MVA_new = (13.8)^2 / 100 = 1.904 Ω
  4. New Per-Unit Impedance (Z_pu,new)Z_pu,old * (V_old/V_new)^2 * (S_new/S_old) = 0.3200 p.u.

What Is the Per-Unit System Impedance Base Conversion Calculator?

Per-unit normalization expresses voltage, current, and impedance as decimal fractions of defined base values.

How Does the Per-Unit System Impedance Base Conversion Calculator Work?

Physical impedance in ohms is conserved while scaling inversely with voltage base squared and directly with apparent power base.

Per-Unit System Impedance Base Conversion Calculator Formula & Variables

The core mathematical equation utilized by this calculator is expressed as:

Z_{ ext{pu,new}} = Z_{ ext{pu,old}} left( rac{V_{ ext{base,old}}}{V_{ ext{base,new}}} ight)^2 left( rac{S_{ ext{base,new}}}{S_{ ext{base,old}}} ight)

Standard formula for shifting per-unit impedance across different power and voltage bases.

How to Use the Per-Unit System Impedance Base Conversion Calculator

  1. Input original nameplate per-unit impedance, original kV and MVA bases, and target new system bases.

Step-by-Step Example Calculation

Transformer Base Conversion to 100 MVA Study Base

Input Values:

zPerUnitOld:0.08
kvBaseOld:13.8
mvaBaseOld:25
kvBaseNew:13.8
mvaBaseNew:100
Worked Steps: New per-unit impedance Z_pu,new = 0.3200 p.u. (physical impedance is 0.609 Ω).

Understanding Your Result

Shows new per-unit impedance along with physical impedance in ohms and original/new base impedances.

Factors That Affect the Result

  • Voltage base mismatches have quadratic impact on per-unit impedance.

When Should You Use This Calculator?

  • Assembling bus admittance matrices (Y-bus) for load flow and short-circuit studies.

Assumptions & Limitations

  • Applies to 3-phase balanced power systems.

Frequently Asked Questions

Calculation Accuracy & Reference Note

Exact power systems per-unit transformation.

Explore more tools and calculators in Math Calculators