Peukert’s Law Battery Capacity & Run Time Calculator

Peukert’s Law describes how a battery available capacity decreases at higher discharge rates due to internal resistance and mass transport limitations.

Manufacturer rated capacity.

Standard rating discharge time (typically 20 hours for C20).

Actual operating load current.

Peukert constant (1.1-1.3 for lead-acid, 1.05 for lithium).

Calculated Result
5.07 hours

Run Time to Cutoff

Run Time in Minutes

303.9 min

Effective Capacity

75.98 Ah

Capacity Retention

76.0 %

Calculation Breakdown

  1. Reference CurrentI_ref = C / H = 100 / 20 = 5.00 A
  2. Peukert Run Timet = H * (I_ref / I)^k = 20 * (5.00 / 15)^1.25 = 5.07 hours

What Is the Peukert’s Law Battery Capacity & Run Time Calculator?

Peukert’s Law expresses the non-linear decrease in usable battery capacity as discharge current increases.

How Does the Peukert’s Law Battery Capacity & Run Time Calculator Work?

High current discharge accelerates electrolyte depletion at the electrode surface, triggering early voltage cutoff.

Peukert’s Law Battery Capacity & Run Time Calculator Formula & Variables

The core mathematical equation utilized by this calculator is expressed as:

t = H \left( \frac{C / H}{I} \right)^k, \quad C_{\text{eff}} = I \times t

Peukert equation relating discharge duration to current and exponent k.

How to Use the Peukert’s Law Battery Capacity & Run Time Calculator

  1. Input manufacturer rated Ah capacity, rated duration hours, actual load current, and Peukert constant k.

Step-by-Step Example Calculation

Lead-Acid Deep Cycle Battery

Input Values:

ratedCapacityAh:100
ratedDischargeHours:20
dischargeCurrentAmps:15
peukertExponentK:1.25
Worked Steps: At 15 A draw, run time is 5.08 hours delivering 76.2 Ah (23.8% capacity penalty).

Understanding Your Result

Outputs expected operating hours before cutoff and effective delivered capacity.

Factors That Affect the Result

  • Higher exponent k increases capacity penalty; lithium chemistries have k close to 1.05.

When Should You Use This Calculator?

  • Off-grid solar inverter battery bank sizing and emergency backup UPS design.

Assumptions & Limitations

  • Assumes constant continuous current at constant temperature.

Frequently Asked Questions

Calculation Accuracy & Reference Note

Standard battery discharge formulation derived by Wilhelm Peukert in 1897.

Explore more tools and calculators in Math Calculators