Room Acoustic Reverberation Time (RT60) Calculator

Reverberation time (RT60) is the duration required for the sound pressure level in an enclosed space to decrease by 60 decibels after the sound source has ceased.

Total interior volumetric space of the room.

Sum of all ceiling, wall, and floor boundary areas.

Mean sound absorption coefficient (0.05 bare drywall/tile to 0.40 acoustically treated).

Atmospheric air absorption coefficient (typically 0.002 m⁻¹ at 1 kHz).

Calculated Result
0.7 s

Eyring Reverberation Time (RT₆₀)

Eyring Reverberation RT₆₀

0.7 seconds

Sabine Reverberation RT₆₀

0.77 seconds

Total Sound Absorption

50.4 metric sabins (m²)

Average Absorption (ᾱ)

0.18

Room Acoustic Environment

IDEAL FOR SPEECH / CLASSROOM (0.4s – 0.8s: high intelligibility, minimal smear)

Calculation Breakdown

  1. Room Volume & Absorption AreaVolume V = 250 m³, Boundary Surface Area S = 280 m² → Total Absorption A = S × ᾱ = 280 × 0.18 = 50.4 metric sabins
  2. Sabine Formulation (Classical Low Absorption)RT₆₀_Sabine = 0.161 × V / A = (0.161 × 250) / 50.4 = 0.77 s
  3. Eyring-Norris Formulation (Accounting for Boundary Decay)RT₆₀_Eyring = 0.161 × V / [-S × ln(1 - ᾱ)] = (0.161 × 250) / [-280 × ln(1 - 0.18)] = 0.7 s

Reverberation Times (s)

Interactive visualization based on your current inputs

RT60
0.00.30.71.01.4Eyring RT₆₀Sabine RT₆₀Speech Target MaxConcert Target MinModelRT60 (s)

What Is the Room Acoustic Reverberation Time (RT60) Calculator?

The Room Acoustic Reverberation Time (RT60) Calculator designs acoustic treatments for recording studios, classrooms, and auditoriums.

How Does the Room Acoustic Reverberation Time (RT60) Calculator Work?

It computes the statistical decay of acoustic sound energy using Sabine and Eyring formulations with high-frequency atmospheric air absorption.

Room Acoustic Reverberation Time (RT60) Calculator Formula & Variables

The core mathematical equation utilized by this calculator is expressed as:

RT_{60, Sabine} = \frac{0.161 V}{A + 4mV}, \quad RT_{60, Eyring} = \frac{0.161 V}{-S \ln(1 - \bar{\alpha}) + 4mV}

Statistical room acoustics decay equations balancing volume sound energy against boundary absorption.

How to Use the Room Acoustic Reverberation Time (RT60) Calculator

  1. Enter room volume in cubic meters.
  2. Specify total interior boundary surface area.
  3. Input the composite average sound absorption coefficient (ᾱ).

Step-by-Step Example Calculation

University Lecture Classroom (250 m³)

Input Values:

roomVolumeM3:250
totalSurfaceAreaM2:280
averageAbsorptionCoeffAlpha:0.18
airAbsorptionCoeffM:0.002
Worked Steps: Eyring RT60 is 0.70 seconds (Sabine: 0.77 s), providing excellent speech intelligibility without acoustic smearing.

Understanding Your Result

RT60 Decay Time: Seconds required for sound to fade by 60 dB.

Acoustic Suitability: Automated classification for speech, orchestral music, or excessive echo.

Factors That Affect the Result

  • Larger room volumes increase RT60, requiring more acoustic paneling to control reverberation.

When Should You Use This Calculator?

  • Classroom acoustic compliance (ANSI/ASA S12.60), home theater design, podcast studio isolation, and church sanctuary renovations.

Assumptions & Limitations

  • Assumes a diffuse sound field where acoustic energy is uniformly distributed throughout the room.

Frequently Asked Questions

Calculation Accuracy & Reference Note

Standard architectural acoustics method per ISO 3382-2.

Explore more tools and calculators in Education Calculators